The following single conductor cable Types and their Outside Diameters (OD) are used by the HST Software when sizing and routing cables for projects in Imperial units for the following cable types:
- String Conductors
- DC Feeders
- LV AC Feeders
- MV AC Feeders
Cable Type | Trade Size (AWG or kcmil) | Cable OD (in) |
600V, Copper, Type PV, XLPE | 12 | .207 |
600V, Copper, Type PV, XLPE | 10 | .231 |
600V, Copper, Type PV, XLPE | 8 | .292 |
600V, Aluminum, Type PV, XLPE | 6 | .319 |
600V, Aluminum, Type PV, XLPE | 4 | .363 |
600V, Aluminum, Type PV, XLPE | 2 | .418 |
600V, Aluminum, Type PV, XLPE | 1 | .488 |
600V, Aluminum, Type PV, XLPE | 1/0 | .527 |
600V, Aluminum, Type PV, XLPE | 2/0 | .564 |
600V, Aluminum, Type PV, XLPE | 3/0 | .611 |
600V, Aluminum, Type PV, XLPE | 4/0 | .660 |
600V, Aluminum, Type PV, XLPE | 250 | .734 |
600V, Aluminum, Type PV, XLPE | 300 | .786 |
600V, Aluminum, Type PV, XLPE | 350 | .827 |
600V, Aluminum, Type PV, XLPE | 400 | .879 |
600V, Aluminum, Type PV, XLPE | 500 | .956 |
600V, Aluminum, Type PV, XLPE | 600 | 1.063 |
600V, Aluminum, Type PV, XLPE | 750 | 1.158 |
600V, Aluminum, Type PV, XLPE | 1000 | 1.310 |
2kV, Copper, Type PV, XLPE | 12 | .237 |
2kV, Copper, Type PV, XLPE | 10 | .261 |
2kV, Copper, Type PV, XLPE | 8 | .312 |
2kV, Copper, Type PV, XLPE | 6 | .349 |
2kV, Copper, Type PV, XLPE | 4 | .396 |
2kV, Copper, Type PV, XLPE | 2 | .456 |
2kV, Copper, Type PV, XLPE | 1 | .531 |
2kV, Copper, Type PV, XLPE | 1/0 | .57 |
2kV, Copper, Type PV, XLPE | 2/0 | .614 |
2kV, Copper, Type PV, XLPE | 3/0 | .664 |
2kV, Copper, Type PV, XLPE | 4/0 | .72 |
2kV, Copper, Type PV, XLPE | 250 | .801 |
2kV, Copper, Type PV, XLPE | 300 | .854 |
2kV, Copper, Type PV, XLPE | 350 | .904 |
2kV, Copper, Type PV, XLPE | 400 | .949 |
2kV, Copper, Type PV, XLPE | 500 | 1.033 |
2kV, Copper, Type PV, XLPE | 600 | 1.139 |
2kV, Copper, Type PV, XLPE | 750 | 1.241 |
2kV, Copper, Type PV, XLPE | 1000 | 1.39 |
2kV, Aluminum, Type PV, XLPE | 6 | .349 |
2kV, Aluminum, Type PV, XLPE | 4 | .396 |
2kV, Aluminum, Type PV, XLPE | 2 | .456 |
2kV, Aluminum, Type PV, XLPE | 1 | .531 |
2kV, Aluminum, Type PV, XLPE | 1/0 | .57 |
2kV, Aluminum, Type PV, XLPE | 2/0 | .614 |
2kV, Aluminum, Type PV, XLPE | 3/0 | .664 |
2kV, Aluminum, Type PV, XLPE | 4/0 | .72 |
2kV, Aluminum, Type PV, XLPE | 250 | .801 |
2kV, Aluminum, Type PV, XLPE | 300 | .854 |
2kV, Aluminum, Type PV, XLPE | 350 | .904 |
2kV, Aluminum, Type PV, XLPE | 400 | .949 |
2kV, Aluminum, Type PV, XLPE | 500 | 1.033 |
2kV, Aluminum, Type PV, XLPE | 600 | 1.139 |
2kV, Aluminum, Type PV, XLPE | 750 | 1.241 |
2kV, Aluminum, Type PV, XLPE | 1000 | 1.39 |
5kV, Aluminum, TRXLPE, 90C, 133% Insulation | 2 | 0.87 |
5kV, Aluminum, TRXLPE, 90C, 133% Insulation | 1 | 0.91 |
5kV, Aluminum, TRXLPE, 90C, 133% Insulation | 1/0 | 0.95 |
5kV, Aluminum, TRXLPE, 90C, 133% Insulation | 2/0 | 0.99 |
5kV, Aluminum, TRXLPE, 90C, 133% Insulation | 3/0 | 1.04 |
5kV, Aluminum, TRXLPE, 90C, 133% Insulation | 4/0 | 1.1 |
5kV, Aluminum, TRXLPE, 90C, 133% Insulation | 250 | 1.15 |
5kV, Aluminum, TRXLPE, 90C, 133% Insulation | 350 | 1.25 |
5kV, Aluminum, TRXLPE, 90C, 133% Insulation | 500 | 1.44 |
5kV, Aluminum, TRXLPE, 90C, 133% Insulation | 750 | 1.63 |
5kV, Aluminum, TRXLPE, 90C, 133% Insulation | 1000 | 1.88 |
15kV, Aluminum, TRXLPE, 90C, 133% Insulation | 2 | 1.08 |
15kV, Aluminum, TRXLPE, 90C, 133% Insulation | 1 | 1.12 |
15kV, Aluminum, TRXLPE, 90C, 133% Insulation | 1/0 | 1.16 |
15kV, Aluminum, TRXLPE, 90C, 133% Insulation | 2/0 | 1.2 |
15kV, Aluminum, TRXLPE, 90C, 133% Insulation | 3/0 | 1.25 |
15kV, Aluminum, TRXLPE, 90C, 133% Insulation | 4/0 | 1.31 |
15kV, Aluminum, TRXLPE, 90C, 133% Insulation | 250 | 1.38 |
15kV, Aluminum, TRXLPE, 90C, 133% Insulation | 350 | 1.48 |
15kV, Aluminum, TRXLPE, 90C, 133% Insulation | 500 | 1.71 |
15kV, Aluminum, TRXLPE, 90C, 133% Insulation | 750 | 1.9 |
15kV, Aluminum, TRXLPE, 90C, 133% Insulation | 1000 | 2.12 |
25kV, Aluminum, TRXLPE, 90C, 133% Insulation | 1 | 1.32 |
25kV, Aluminum, TRXLPE, 90C, 133% Insulation | 1/0 | 1.38 |
25kV, Aluminum, TRXLPE, 90C, 133% Insulation | 2/0 | 1.42 |
25kV, Aluminum, TRXLPE, 90C, 133% Insulation | 3/0 | 1.47 |
25kV, Aluminum, TRXLPE, 90C, 133% Insulation | 4/0 | 1.53 |
25kV, Aluminum, TRXLPE, 90C, 133% Insulation | 250 | 1.59 |
25kV, Aluminum, TRXLPE, 90C, 133% Insulation | 350 | 1.75 |
25kV, Aluminum, TRXLPE, 90C, 133% Insulation | 500 | 1.91 |
25kV, Aluminum, TRXLPE, 90C, 133% Insulation | 750 | 2.13 |
25kV, Aluminum, TRXLPE, 90C, 133% Insulation | 1000 | 2.32 |
35kV, Aluminum, TRXLPE, 90C, 133% Insulation | 1/0 | 1.58 |
35kV, Aluminum, TRXLPE, 90C, 133% Insulation | 2/0 | 1.63 |
35kV, Aluminum, TRXLPE, 90C, 133% Insulation | 3/0 | 1.74 |
35kV, Aluminum, TRXLPE, 90C, 133% Insulation | 4/0 | 1.8 |
35kV, Aluminum, TRXLPE, 90C, 133% Insulation | 250 | 1.85 |
35kV, Aluminum, TRXLPE, 90C, 133% Insulation | 350 | 1.98 |
35kV, Aluminum, TRXLPE, 90C, 133% Insulation | 500 | 2.15 |
35kV, Aluminum, TRXLPE, 90C, 133% Insulation | 750 | 2.33 |
35kV, Aluminum, TRXLPE, 90C, 133% Insulation | 1000 | 2.53 |