  4. BASIS OF DESIGN > ELECTRICAL ENGINEERING
  5. CONDUCTOR PROPERTIES DATABASE – IMPERIAL UNITS

CONDUCTOR PROPERTIES DATABASE – IMPERIAL UNITS

The following conductor properties are used by the HST Software when sizing conductors for projects in Imperial units for the following cable types:

  • String Conductors
  • DC Feeders
  • LV AC Feeders
  • MV AC Feeders
  • Bare Ground Conductors
Trade Size Area (mm^2) Diameter (mm) No. Strands Unit
18 0.823 1.21 7 AWG
16 1.31 1.53 7 AWG
14 2.08 1.85 7 AWG
12 3.31 2.32 7 AWG
10 5.261 2.95 7 AWG
8 8.367 3.71 7 AWG
6 13.3 4.67 7 AWG
4 21.15 5.89 7 AWG
3 26.67 6.6 7 AWG
2 33.62 7.42 7 AWG
1 42.41 8.43 19 AWG
1/0 53.49 9.45 19 AWG
2/0 67.43 10.62 19 AWG
3/0 85.01 11.94 19 AWG
4/0 107.2 13.41 19 AWG
250 127 14.61 37 AWG
300 152 16 37 kcmil
350 177 17.3 37 kcmil
400 203 18.49 37 kcmil
500 253 20.65 37 kcmil
600 304 22.68 61 kcmil
700 342 24.015 61 kcmil
750 380 25.35 61 kcmil
800 443.5 27.305 61 kcmil
900 475.25 28.2825 61 kcmil
1000 507 29.26 61 kcmil
1250 633 32.74 91 kcmil
1500 760 35.86 91 kcmil
1750 886.5 38.655 91 kcmil
2000 1013 41.45 127 kcmil

 

 

The following conductor properties are used by the HST Software when sizing conductors for projects in Imperial units for the following cable types:

  • Overhead Conductors
Trade Size Area (mm^2) Diameter (mm) No. Strands Unit
397 201 0.743 18 kcmil
477 241 0.814 18 kcmil
556 281 0.879 18 kcmil
636 322 0.94 18 kcmil
795 402 1.04 36 kcmil
954 483 1.165 45 kcmil
1272 644 1.345 45 kcmil
1590 805 1.504 45 kcmil
1780 902 1.602 84 kcmil
2167 1098 1.735 84 kcmil